4Ć46 FST Configuration
Original Ć June 1990CE4.2:CL6211
AOUT AOUT
11
INSTRUCTION NAME: AOUT (analog output)
DESCRIPTION : The analog output will be 4 to 20 milliamps or 1 to 5 volts dc for an SVA input
span of 0 to 100 percent, depending upon which output channel number is selected. The SVA
and SVD inputs remain unchanged. Therefore, the SVA input is available for use in the next
function.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
100
0
t
0
t
1
INPUT
t
0
t
1
OUTPUT
20 mA
4 mA
(1 VDC)
(5 VDC)
f (x)
CONFIGURATION FORMAT: AOUT (
AOUT channel >>
Comment >>
OPERAND DESCRIPTIONS:
AOUT channel - The channel number of the desired analog output. The type and number of
outputs for each controller are as follows:
AOUT channel number
Controller type 1 2 3 4 5 6
Computing (1) CO+(2) VO+(2)
2-Wide CO1+ CO2+ VO1+
3-Wide Discrete CO1+ CO2+ VO1+
3-Wide Analog CO1+ CO2+ VO1+ CO4+ VO2+
4-Wide CO1+ CO2+ VO1+ CO3+ CO4+ VO2+
(Continued on next page)