4Ć95FST Configuration
Original Ć June 1990 CE4.2:CL6211
ICPLDD ICPLDD
42
INSTRUCTION NAME: ICPLDD (indirect control point load discrete)
DESCRIPTION: This instruction sets the SVD output equal to the discrete indirect control point
(ICP) value contained in operand 2. Operand 1 contains the ICP name. The SVA input remains
unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
ICP - OPERAND 1
REGISTER
1234
OPERAND 2
T
CONFIGURATION FORMAT: ICPLDD (
ICP tag >>
ICP reg number >>
Comment >>
OPERAND DESCRIPTIONS:
ICP tag - The tag of the ICP.
ICP reg number - The number of the ICP operating data register that contains the ICP value.
There are four discrete registers available, numbered 1 to 4.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVD(out) = ICP value
SVA(out) = SVA(in)
Comentários a estes Manuais