4Ć8 Device Definition Configuration
Original Ć June 1990CE4.2:CL6211
4.2.2 Aux EU Definition
This portion of configuration defines engineering unit end points for
signal parameters that are used in certain functions in the FST that
perform scaling. Auxiliary engineering unit (AUX EU) definition provides
extra capacity for signal parameters that are not scaled using indirect
control point (ICP) or direct control point (DCP) engineering units. For
example, if two analog input signals that are summed together have
different units, and only one of the two is scaled in an ICP, then the end
points of the other analog input are listed as an auxiliary engineering unit
pair.
Type Ċ The type of the controller that is currently being configured. This
is a read only field displaying the type that was entered in the previous
device definition phase of configuration.
No. Ċ The numbers of the 20 AUX EUs are listed in this read only field.
Note that the first 10 are available for both computing and interactive
controllers, while the second 10 (11 through 20) are available for the
interactive controller only.
Name Ċ The name of the AUX EU. This can be up to 8 characters in
length. The name must be unique to the controller.
High Scale Value Ċ The number to be used as the 100% value for the
auxiliary engineering unit. This value can be any valid floating point
number.
Low Scale Value Ċ The number to be used as the 0% value for the
auxiliary engineering unit. This value can be any valid floating point
number.
4.2.3 Operator Stations Definition
This portion of configuration defines the operator station ports that are
connected to panel-mounted, Controller Operator Station Units. Both
the type of operator station and the direct control point (DCP) or points
to be displayed on the operator station are identified. If no operator
stations are connected to the controller, operator station definition is not
required.
Type Ċ The type of the controller that is currently being configured. This
is a read only field displaying the type that was entered in the previous
device definition phase of configuration.
Port No. Ċ The port number of the operator station(s) that the controller
currently being configured will utilize. A computing controller has one
operator station port. An interactive controller has two, four, or six ports
depending on whether the controller is a 2-,3-, or 4-wide model.