4Ć6 Device Definition Configuration
Original Ć June 1990CE4.2:CL6211
4.2 Device Definition
IAC and Computing Controller device definition consists of completing
the main device definition form, and associated forms to define FST
Registers, Operator Stations, and Auxiliary Engineering Units.
The main device definition form identifies the physical location of the data
concentrator unit, to which the controller is connected, on the PRoVOX
data highway and the controller type.
Type Ċ This field defines the controller type. Valid types are:
COMPUTING, IAC2, IAC3 ANALOG, IAC3 DISCRETE or IAC4.
Highway No. Ċ The highway number is the number of the data highway
that the data concentrator unit (DCU), to which the controller is
connected, communicates on. Valid highway numbers are 0 through 8.
Device No. Ċ The device number is the number of the communications
interface assembly (CIA) of the data concentrator unit (DCU), to which
the controller is connected. If the highway number is 0, valid device
numbers are 1 through 6. If the highway number is 1 through 8, valid
device numbers are 1 through 30.
Port No. Ċ The port number is the number of the data concentrator port
to be assigned to this controller. The port numbers correspond to the
card slots of the controller card files. If two simplex (non-redundant)
card files are connected to a data concentrator, ports 1 through 8 are
assigned to the card slots of one file, and ports 9 through 16 are
assigned to the card slots of the other file. If four redundant card files
are connected to a data concentrator, ports 1 through 4 are assigned to
the like-numbered pairs of primary and secondary card slots of the first
file, ports 5 through 8 are assigned to the like-numbered pairs of
primary and secondary card slots of the second file, and so on. Valid
port numbers are 1 through 16 (see note below).
Note
For an interactive controller, the port number
corresponding to the card slot position of the
MPU card must be selected. For example, if a
four-wide interactive controller is installed in
slots 1 through 4 of the first card file (simplex
or redundant), port number 4 is selected (the
MPU card is always in the right-most slot).
Not all ports are valid for interactive controllers
(i.e. no variety of interactive controller can
reside in port 1).